Measurement line type |
Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement) |
Voltage ranges |
Voltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak |
Current ranges |
50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use) |
Power ranges |
50.000 W to 6.0000 MW (determined automatically based on current range in use) |
Basic accuracy |
Voltage: ±0.2% of nominal voltage, Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy, Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy, AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy |
Measurement items |
1. Transient over voltage : 200 kHz sampling
2. Frequency cycle : Calculated as one cycle
3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle
4. Voltage swell, Voltage dips, Voltage interruption, RVC (Ver. up) : Voltage (1/2) RMS calculation
5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.
6. Frequency 200 ms: Calculated as 10 or 12 cycles
7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period
8. Voltage waveform peak, Current waveform peak
9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor
10. Voltage crest factor, Current crest factor
11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders
12. Harmonic voltage-current phase angle: 1 th to 50 th orders
13. Total harmonic distortion factor (voltage/ current)
14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders
15. K Factor (multiplication factor)
16. IEC Flicker, Δ V10 Flicker |
Record |
Maximum recording interval: 1 year, Maximum number of recordable events: 9999 × 365 days |
Interfaces |
SD/SDHC memory card, RS-232C (for communication/ LR8410 link), LAN (HTTP server/ FTP/ Send e-mail), USB 2.0 (for communication) |
Logger connectivity |
Sends measured values wirelessly to logger by using a Bluetooth® wireless technology serial conversion adapter. (Supported devices: Hioki LR8410 Link-compatible loggers), Ver. 2.0 and later |
Display |
6.5-inch TFT color LCD (640 × 480 dots) |
Power supply |
AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter) |
Dimensions and mass |
300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack) |
Accessories |
Instruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color clip (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1 |